1. Uzstādiet izpildmehānismu uz vārsta

  1. Turn the valve in fully closed position.
  2. Install the bracket on the valve.
  3. Connect the coupling on the valve shaft.
  4. Drive the actuator to the fully closed position with manual handle.
  5. Insert the actuator output shaft into the square hole of the coupling.
  6. Tighten the connecting between these parts.
  7. Drive the actuator with manual handle to in the travel range, checking if turning smooth.

 

Attention: make sure the concentricity of connection shaft in the mounting process and do not use excessive force.

More Details >

2. Pārbaudiet mehānisko ierobežotāju

  • The mechanical limiter has been set in the right position after manufacturing.
  • Normally we just need to double-check the space between the full open/close position and the mechanical limit position is more than 2.5° after installation.
  • Make a slightly adjustment if necessary.

3. Elektroinstalācija

  • Use a shield wire for 4-20mA signal
  • Separate 4-20mA signal line from power line
  • Head the wire downwards to avoid water infiltration

4. Iestatiet atvēršanas/aizvēršanas gala pozīciju

  • Turn S-A to 2.
  • Pilnībā aizvērtas pozīcijas konfigurēšana
    • Press the Open/Shut button to drive the valve to the fully closed position.
    • Hold the Set button and then the Shut button until L2 is turned on which means the fully closed position configuration is done.
    • Now you could release these 2 buttons.
  • Pilnībā atvērtas pozīcijas konfigurēšana
    • Press the Open/Shut button to drive the valve to the fully open position.
    • Hold the Set button and then the Open button until L2 is turned on which means the fully open position configuration is done.
    • Now you could release these 2 buttons.

 

Piezīme: Ja pilnībā atvērtā un aizvērtā pozīcija ir konfigurēta ar vienu un to pašu pozīciju, konfigurācija tiks veiksmīgi veikta. Taču izpildmehānisms modulācijas režīmā negriezīsies.

5. Sāciet lietot

  • Turn S-A to 1 to start modulation