Technical Parameters
| Explosion Proof Grade | Exd II CT4Gb |
| Power Supply | DC24V, AC110V, AC220V, AC380V |
| Standard Torque/Time | DC24V: 200Nm/60S AC110V/AC220V/AC380V: 200Nm/30S |
| Optional Torque/Time | 50Nm/15S, 200Nm/60S |
| Rotation Angle Range | Adjustable from 0 to 90 degrees |
| Motor Power/Current | DC24V: 25W/3.12A AC110V: 40W/0.63A AC220V: 40W/0.35A AC380V: 30W /0.19A |
| Control Circuit | Type A/B/C/D/E/F/G/H |
| Weight | 5.5kg |
| Insulation Resistance | DC24V: 100MΩ/250VDC AC110V/AC220V/AC380V: 100MΩ/500VDC |
| Withstand Voltage | DC24V/AC24V: 500VAC for 1 minute |
| Water Proof Level | IP68 |
| Installation | 360 ° installation at any angle |
| Electrical Interface | 2-M20x1.5 explosion-proof plug, users should install corresponding explosion-proof cable connectors according to the selected cable during use |
| Working Temperature | -20℃~﹢60℃ |
| Optional Function | ♦ Over torque protection ♦ Dehumidification heater |
| Modulation Parameters | |
| Señal de entrada | 4~20mA, 0~10V arbitrary calibration |
| output Signal | 4~20mA, 0~10V arbitrary calibration |
| Bus | 485/Modbus/CAN |
| Internet of Things | WIFI/LoRA/4G |
| Basic Error | ≤±1% |
| Return Error | ≤1% |
| Hysteresis | Adjustable from 0.5% to 5.0% |
| Reposition Times | 0 times |
| Repeatability Error | ≤1% |
Dimensions
Application Circuit
Modulación
E - Modulación con una unidad de control
- Entrada: 4~20 mA / 0~10 V
- Salida: 4~20 mA / 0~10 V
- Bus de campo: Modbus / CAN
- IIoT: DTU WIFI/LoRA/4G
Connecting Details:
- Connecting AC85-220V supply power line to L and neutral to N.
- Connecting 4-20mA/2-10V input signal source from control system to input-/+.
- Connecting Output -/+ to the system to send out the real-time valve position.
Avances y posicionamiento
F - Con una unidad de posicionamiento
- Controlar el actuador para abrir o cerrar con K
- The real-time valve position will be send out as a 4-20mA signal.
Connecting Details:
- Connecting AC85-220V supply power line to L and neutral to N.
- Switch AC85-220V line to CLOSE(P2) to close the valve.
- Switch AC85-220V line to OPEN(P3) to open the valve.
- Connecting Output -/+ to the system to send out the real-time valve position.
C - Con un potenciómetro de 1 kΩ/500 Ω
- Controlar el actuador para abrir o cerrar con K
- La posición de la válvula en tiempo real se enviará como un valor de resistencia del potenciómetro.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the low side of potentiometer that is normally connected to signal GND.
- Connecting signal input of control system to P5. The resistance value between P4 and P5 will become higher as actuator opening the valve, while the value between P5 and P6 will become lower.
- P6 is the high side of potentiometer that is normally connected to signal power.
- Connect earth to P7.
D - Con un potenciómetro y retroalimentación de posición final.
- Controlar el actuador para abrir o cerrar con K
- La posición de la válvula en tiempo real se enviará como un valor de resistencia del potenciómetro.
- El terminal de salida de la posición final APERTURA/CIERRE enviará el evento como una señal pasiva cuando se alcance la posición final.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P5 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P6 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- P7 is the low side of potentiometer that is normally connected to signal GND.
- Connecting signal input of control system to P8. The resistance value between P7 and P8 will become higher as actuator opening the valve, while the value between P8 and P9 will become lower.
- P9 is the high side of potentiometer that is normally connected to signal power.
- Connect earth to P12.
ENCENDIDO - APAGADO
A - Con 2 salidas de señal de posición final activas
- Controlar el actuador para abrir o cerrar con K
- El terminal de salida de la posición final APERTURA/CIERRE enviará el evento como una señal activa de 220 VCA cuando se alcance la posición final.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P5 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of open.
- P6 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of close.
- Connect earth to P7.
B - Con 2 interruptores de posición final pasivos
- Controlar el actuador para abrir o cerrar con K
- El terminal de salida de la posición final APERTURA/CIERRE enviará el evento como una señal pasiva cuando se alcance la posición final.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P5 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P6 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P7.
G - Motor de CC con 2 interruptores de posición final.
- Controla el actuador para que se abra o se cierre mediante la dirección de la alimentación eléctrica entre los terminales 1 y 2.
- El terminal de salida de la posición final APERTURA/CIERRE enviará el evento como una señal pasiva cuando se alcance la posición final.
Connecting Details:
- Connecting DC24V+ to P1 and DC24V- to P2 to close the valve.
- Connecting DC24V+ to P2 and DC24V- to P1 to close the valve.
- P3 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P4 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P5 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P7.
Motor H - trifásico de 380 VCA con 2 interruptores de posición final.
- Controlar el actuador para abrirlo o cerrarlo mediante un inversor externo para cambiar la fase de la alimentación eléctrica.
- El terminal de salida de la posición final APERTURA/CIERRE enviará el evento como una señal pasiva cuando se alcance la posición final.
Connecting Details:
- Connecting a 3 phase AC380V inverter output to P1, P2 and P3, then the actuator can be controlled to open or close the valve by change the 3 phase order.
- Connecting AC380V neutral to N(P4).
- P5 is used for cooperating with an external switch to control the inverter 3 phase order. This terminal is connected to N(P4) when actuator is not in end-position of CLOSE and disconnected from N(P4) after actuator reached end-position of CLOSE.
- P6 is used for cooperating with an external switch to control the inverter 3 phase order. This terminal is connected to N(P4) when actuator is not in end-position of OPEN and disconnected from N(P4) after actuator reached end-position of OPEN.
- P7 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P8 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P9 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P12.
Nota:
- El circuito dentro del recuadro punteado es el circuito interno del actuador. El circuito exterior muestra la conexión eléctrica para el funcionamiento del actuador.
- Si tiene otros requisitos específicos sobre la conexión del circuito, no dude en ponerse en contacto con nuestro servicio de asistencia técnica.
Choose another actuator with different torque
50 Nm/20 S
————————–
Opcional con
20Nm/4S
30 Nm/10 S
50 Nm/60 S
100 Nm/30 s
————————–
Opcional con
50 Nm/15 S
100 Nm/60 s
200 Nm/30 s
————————–
Opcional con
100 Nm/15 S
200 Nm/60 s
400 Nm/30 s
————————–
Opcional con
200 Nm/15 S
400 Nm/60 s