Technical Parameters
| Power Supply | DC24V, AC24V, AC110V, AC220V, AC380V |
| Standard Torque/Time | 600 Nm/45 s |
| Rotation Angle Range | Adjustable from 0 to 90 degrees |
| Motor power | DC24V:70W/6.04A AC24V:90W/6.80A AC110V:90W/1.18A AC220V:90W/0.6A AC380V:40W/0.29A |
| Control Circuit | Type A/B/C/D/E/F/G/H |
| Weight | 10Kg |
| Insulation Resistance | DC24V/AC24V: 100MΩ/250VDC AC110V/AC220V/AC380V: 100MΩ/500VDC |
| Withstand Voltage | DC24V/AC24V: 500VAC for 1 minute |
| Water Proof Level | IP67 |
| Installation | 360 ° installation at any angle |
| Electrical Interface | G1/2 waterproof cable connector: one power line and one signal line each |
| Working Temperature | -25℃ ~ +55℃ |
| Optional Function | Over torque protection, dehumidification heater, convex indicator, operating handwheel |
| Modulation Parameters | |
| Signal d'entrée | 4~20mA, 0~10V arbitrary calibration |
| output Signal | 4~20mA, 0~10V arbitrary calibration |
| Bus | 485/Modbus/CAN |
| Internet of Things | WIFI/LoRA/4G |
| Basic Error | ≤±1% |
| Return Error | ≤1% |
| Hysteresis | Adjustable from 0.5% to 5.0% |
| Reposition Times | 0 times |
| Repeatability Error | ≤1% |
Dimensions
Application Circuit
Modulation
E - Modulation avec une unité de contrôle
- Entrée : 4~20 mA / 0~10 V
- Sortie : 4~20 mA / 0~10 V
- Bus de terrain : Modbus / CAN
- IIoT : DTU WiFi/LoRa/4G
Connecting Details:
- Connecting AC85-220V supply power line to L and neutral to N.
- Connecting 4-20mA/2-10V input signal source from control system to input-/+.
- Connecting Output -/+ to the system to send out the real-time valve position.
Avancement par à-coups et positionnement
F - Avec une unité de positionnement
- Actionneur de commande pour ouvrir ou fermer avec K
- The real-time valve position will be send out as a 4-20mA signal.
Connecting Details:
- Connecting AC85-220V supply power line to L and neutral to N.
- Switch AC85-220V line to CLOSE(P2) to close the valve.
- Switch AC85-220V line to OPEN(P3) to open the valve.
- Connecting Output -/+ to the system to send out the real-time valve position.
C - Avec un potentiomètre 1KΩ/500Ω
- Actionneur de commande pour ouvrir ou fermer avec K
- La position de la vanne en temps réel sera transmise sous forme de valeur de résistance du potentiomètre.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the low side of potentiometer that is normally connected to signal GND.
- Connecting signal input of control system to P5. The resistance value between P4 and P5 will become higher as actuator opening the valve, while the value between P5 and P6 will become lower.
- P6 is the high side of potentiometer that is normally connected to signal power.
- Connect earth to P7.
D - Avec un potentiomètre et un retour de position finale
- Actionneur de commande pour ouvrir ou fermer avec K
- La position de la vanne en temps réel sera transmise sous forme de valeur de résistance du potentiomètre.
- La borne de sortie de la position finale OUVERTE/FERMÉE enverra l'événement sous forme de signal passif lorsque la position finale sera atteinte.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P5 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P6 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- P7 is the low side of potentiometer that is normally connected to signal GND.
- Connecting signal input of control system to P8. The resistance value between P7 and P8 will become higher as actuator opening the valve, while the value between P8 and P9 will become lower.
- P9 is the high side of potentiometer that is normally connected to signal power.
- Connect earth to P12.
MARCHE - ARRÊT
A - Avec 2 sorties de signal de position finale actives
- Actionneur de commande pour ouvrir ou fermer avec K
- La borne de sortie de la position finale OUVERTE/FERMÉE enverra l'événement sous la forme d'un signal actif de 220 V CA lorsque la position finale sera atteinte.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P5 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of open.
- P6 is end-position OPEN terminal which will output a AC220V source which can be used to drive an Indication light when actuator reached end-position of close.
- Connect earth to P7.
B - Avec 2 interrupteurs de fin de course passifs
- Actionneur de commande pour ouvrir ou fermer avec K
- La borne de sortie de la position finale OUVERTE/FERMÉE enverra l'événement sous forme de signal passif lorsque la position finale sera atteinte.
Connecting Details:
- Connecting AC85-220V supply power neutral to P1.
- Switch AC85-220V line to CLOSE(P2) to close the valve
- Switch AC85-220V line to OPEN(P3) to open the valve.
- P4 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P5 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P6 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P7.
Moteur à courant continu G avec 2 interrupteurs de fin de course
- Actionneur de commande pour s'ouvrir ou se fermer en fonction du sens d'alimentation entre les bornes 1 et 2
- La borne de sortie de la position finale OUVERTE/FERMÉE enverra l'événement sous forme de signal passif lorsque la position finale sera atteinte.
Connecting Details:
- Connecting DC24V+ to P1 and DC24V- to P2 to close the valve.
- Connecting DC24V+ to P2 and DC24V- to P1 to close the valve.
- P3 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P4 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P5 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P7.
Moteur triphasé 380 V CA H avec 2 interrupteurs de fin de course
- Actionneur de commande permettant l'ouverture ou la fermeture par un onduleur externe afin de modifier la phase de l'alimentation électrique.
- La borne de sortie de la position finale OUVERTE/FERMÉE enverra l'événement sous forme de signal passif lorsque la position finale sera atteinte.
Connecting Details:
- Connecting a 3 phase AC380V inverter output to P1, P2 and P3, then the actuator can be controlled to open or close the valve by change the 3 phase order.
- Connecting AC380V neutral to N(P4).
- P5 is used for cooperating with an external switch to control the inverter 3 phase order. This terminal is connected to N(P4) when actuator is not in end-position of CLOSE and disconnected from N(P4) after actuator reached end-position of CLOSE.
- P6 is used for cooperating with an external switch to control the inverter 3 phase order. This terminal is connected to N(P4) when actuator is not in end-position of OPEN and disconnected from N(P4) after actuator reached end-position of OPEN.
- P7 is the COM for passive contact signal of end-position OPEN/CLOSE which is normally connected to signal GND.
- P8 is end-position OPEN terminal which will be connected to COM when actuator reached end-position of open.
- P9 is end-position CLOSE terminal which will be connected to COM when actuator reached end-position of close.
- Connect earth to P12.
Note:
- Le circuit à l'intérieur du cadre en pointillés représente le circuit interne de l'actionneur. Le circuit extérieur illustre le branchement électrique nécessaire à l'utilisation de l'actionneur.
- Si vous avez d'autres exigences spécifiques concernant le raccordement du circuit, n'hésitez pas à contacter notre assistance technique.
Choose another actuator with different torque
50 Nm/20 s
————————–
Optionnel avec
20 Nm/4 S
30 Nm/10 s
50 Nm/60 s
50 Nm/100 s
100 Nm/30 s
————————–
Optionnel avec
50 Nm/15 s
100 Nm/60 s
200 Nm/30 s
————————–
Optionnel avec
100 Nm/15 s
200 Nm/60 s
400 Nm/30 s
————————–
Optionnel avec
200 Nm/15 s
400 Nm/60 s
1000 Nm/30 s
————————–
Optionnel avec
1000 Nm/30 s
500 Nm/15 s